Steel layer-stranded cables
DIN 48201-3, EN 50182, CSN024305
Steel layer-stranded cables are mainly used as earthing and lightning arrester conductors. Layer-stranded cables are made of galvanized steel wire with a galvanized surface, and with single or multiple layers of strands. The stranding direction of the outer layer of the cable is always to the right. The layer-stranded cables can be delivered according to MSZ, DIN, BS etc. standards.
The table below shows the technical parameters of the stranded cables according to MSZ 48201 standards.
Nominal section mm² |
Actual section mm² |
Wire diameter | Number of wires/td> | Stranded wire diameter mm |
Weight kg/km |
Calculated tensile strength, kN ST II. | Calculated tensile strength, kN ST III. |
25 | 24.25 | 2.1 | 7 | 6.3 | 192 | 15.89 | 30.40 |
35 | 34.36 | 2.5 | 7 | 7.5 | 272 | 22.52 | 43.08 |
50 | 49.48 | 3.0 | 7 | 9.0 | 391 | 32.43 | 62.04 |
50 | 48.36 | 1.8 | 19 | 9.0 | 384 | 31.69 | 60.65 |
70 | 65.82 | 2.1 | 19 | 10.5 | 523 | 43.14 | 82.53 |
95 | 93.27 | 2.5 | 19 | 12.5 | 741 | 61.13 | 116.90 |
120 | 117.00 | 2.8 | 19 | 14.0 | 930 | 76.69 | 146.70 |
150 | 147.10 | 2.25 | 37 | 15.7 | 1171 | 96.42 | 184.40 |
185 | 181.60 | 2.5 | 37 | 17.5 | 1447 | 119.00 | 227.70 |
240 | 242.50 | 2.25 | 61 | 20.2 | 1935 | 158.90 | 304.10 |