Bronze layer-stranded cables are mainly used for erection of overhead electric lines, where our product also has a suspending role. Bronze stranded wires are made of CuMg 0,4 alloy material with single or multi-layer stranding. The specifications of the raw material, wires and strands of the product are in the following standards:

  • DIN 17666 Bz II (CuMg 0,4)
  • DIN 48200 Part 2
  • DIN 48201 Page 2
termékek bronzsodratok01
termékek bronzsodratok02
termékek bronzsodratok03
termékek bronzsodratok04

The following table shows the technical parameters of the DIN standard bronze (Bz II) suspending layer-stranded cables.

Nominal section
mm²
Actual section
mm²
Number of wires
db
Wire diameter
mm
Stranded wire diameter
mm
Weight
kg/km
Calculated tensile strength
kp
Current
A
10 10.2 7 1.35 4.1 90 5.88 75
16 15.89 7 1.7 5.1 143 9.33 100
25 24.25 7 2.1 6.3 218 14.24 130
35 34.36 7 2.5 7.5 310 20.17 160
50 49.48 7 3 9 446 28.58 200
50 48.35 19 1.8 9 437 28.39 200
70 65.81 19 2.1 10.5 596 38.64 245
95 93.27 19 2.5 12.5 845 54.76 305
120 116.99 19 2.8 14 1060 67.57 350
150 147.11 37 2.25 15.8 1337 86.37 410
185 181.62 37 2.5 17.5 1649 106.63 465
240 242.54 61 2.25 20.3 2209 142.4 560
300 299.43 61 2.5 22.5 2725 175.8 635
400 400.14 61 2.89 26 3640 231.12 765