Steel-aluminum layer-stranded cables

EN 50182, ÖNORM E 4004, MSZ-149/4

 

They are mainly used for high-voltage transmission lines, mounted on insulators on poles. The layer-stranded cables consist of galvanized steel wire or a galvanized steel core and one or more layers of aluminum cores stranded around it. We can deliver the layer-stranded cables according to the MSZ 149/4, DIN 48204, BS 215, CSA C49 standards etc. In addition, we also manufacture all sizes and structures according to the European standards in force, in accordance with EN 50182.

The table below shows the technical parameters of the layer-stranded cables made according to MSZ 149/4 standard.

Nominal section
mm²
Number of steel wires
db
Steel wire diameter
mm
Number of
steel wires
Alu wire diameter
mm
Rate of section
AI/Ac
External diameter, mm. Calculated weight
kg/km
Calculated tensile strength
kN
Electric resistance at
20 C
Ohm/km
16/2,5 1 1,80 6 1,80 6 5,40 62 5,91 1,862
25/4 1 2,25 6 2,25 6 6,75 96 9,00 1,192
35/6 1 2,70 6 2,70 6 8,10 139 12,68 0,8270
50/8 1 3,20 6 3,20 6 9,60 194 17,48 0,5887
90/15 7 1,67 26 2,15 6,16 13,61 386 35.75 0,3119
120/20 7 1,90 26 2,45 6,16 15,50 501 45,85 0,2402
150/25 7 2,10 26 2,70 6,16 17,10 608 55,25 0,1978
185/30 7 2,33 26 3,00 6,16 18,99 751 66,20 0,1602
240/40 7 2,68 26 3,45 6,16 21,84 983 85,34 0,1211
250/40 7 2,80 26 3,50 6,16 22,40 1089 84,00 0,0173
300/50 7 3,00 26 3,86 6,16 24,44 1240 106,98 0,0967
400/53 7 3,10 54 3,1 7,71 27,90 1562 131,30 0,0725
500/66 7 3,45 54 3,45 7,71 31,05 1935 157,50 0,0585
625/82 7 3,84 54 3,84 7,71 34,56 2396 192,70 0,04773
70/40 7 2,70 12 2,7 1,71 13,50 507 58,57 0,4276
95/56 7 3,20 12 3,2 1,71 16,00 713 81,55 0,3044
120/70 7 3,60 12 3,6 1,71 18,00 901 199,50 0,2405